Siddik, Muhammad Abu Bakar and Nawawi, Zainuddin and Husin, Ahmad and Buntat, Zolkafle and Jambak, Muhammad Irfan and Malek, Z.A and Bashir, N and Zarin, M.I.A (2011) Induced Voltage on Objects under Six-Phase Transmission Line. Prosiding TENCON 2011. ISSN 978-1-4577-0254-9/ IEEE
Preview |
Text
05_PAPER_TENCON_2011_SIX_PHASE-ABBS-ZN-MIJ.pdf Download (875kB) | Preview |
Abstract
This paper presents results of an experimental investigation on voltage induced on objects under a sixphase transmission line due to line switching incidences. In this work, the voltage induced on a vertical receiver and a pipeline due to line energization and de-energization in a six-phase power transmission line system is reported. The research was carried out using a six-phase transmission line mock-up system with ratio of 5/132 kV. The results showed that the induced voltage on the objects is less than 4 kV. In addition the high induced voltage experienced by the vertical receiver was from the left side of the phase composition while the pipeline experienced higher induced voltage from the right side phase composition.
Item Type: | Article |
---|---|
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1-9971 Electrical engineering. Electronics. Nuclear engineering > TK1 Electrical engineering--Periodicals. Automatic control--Periodicals. Computer science--Periodicals. Information technology--Periodicals. Automatic control. Computer science. Electrical engineering. Information technology. |
Divisions: | 03-Faculty of Engineering > 20201-Electrical Engineering (S1) |
Depositing User: | Prof Zainuddin Nawawi |
Date Deposited: | 20 Nov 2019 04:17 |
Last Modified: | 20 Nov 2019 04:17 |
URI: | http://repository.unsri.ac.id/id/eprint/16723 |