PRATIWI, RANI RAMADHANI EKA and Caroline, Caroline (2019) PENGARUH PROSES PENGISIAN (CHARGING) BATERAI TERHADAP EFISIENSI UPS (UNINTERRUPTIBLE POWER SUPPLY) DI PT. PUPUK SRIWIDJAJA AREA 2B PALEMBANG. Undergraduate thesis, Sriwijaya University.
Text
RAMA_20201_03041181520022.pdf - Accepted Version Restricted to Repository staff only Available under License Creative Commons Public Domain Dedication. Download (3MB) | Request a copy |
|
Text
RAMA_20201_03041181520022_TURNITIN.pdf - Accepted Version Restricted to Repository staff only Available under License Creative Commons Public Domain Dedication. Download (3MB) | Request a copy |
|
Preview |
Text
RAMA_20201_03041181520022_0025017706_01_front_ref.pdf - Accepted Version Available under License Creative Commons Public Domain Dedication. Download (778kB) | Preview |
Text
RAMA_20201_03041181520022_0025017706_02.pdf - Accepted Version Restricted to Repository staff only Available under License Creative Commons Public Domain Dedication. Download (390kB) | Request a copy |
|
Text
RAMA_20201_03041181520022_0025017706_03.pdf - Accepted Version Restricted to Repository staff only Available under License Creative Commons Public Domain Dedication. Download (312kB) | Request a copy |
|
Text
RAMA_20201_03041181520022_0025017706_04.pdf - Accepted Version Restricted to Repository staff only Available under License Creative Commons Public Domain Dedication. Download (398kB) | Request a copy |
|
Text
RAMA_20201_03041181520022_0025017706_05.pdf - Accepted Version Restricted to Repository staff only Available under License Creative Commons Public Domain Dedication. Download (37kB) | Request a copy |
|
Text
RAMA_20201_03041181520022_0025017706_06_ref.pdf - Bibliography Restricted to Repository staff only Available under License Creative Commons Public Domain Dedication. Download (145kB) | Request a copy |
|
Text
RAMA_20201_03041181520022_0025017706_07_lamp.pdf - Accepted Version Restricted to Repository staff only Available under License Creative Commons Public Domain Dedication. Download (2MB) | Request a copy |
Abstract
As the largest fertilizer producer industry in South Sumatera, an UPS (Uninterruptible Power Supply) system is needed at PT Pupuk Sriwidjaja Palembang as a back up power at critical loads. Batteries on UPS systems have an important role as a store of electrical energy that can be used at any time when there is a problem with the main power source so that a good charging system is needed. This study aims to determine the battery charging process and the efficiency value of the UPS when it is supplying power. From 174 battery cells, nearly all of Nickel Cadmium battery cells that are used as energy storage on the UPS show optimal voltage values which are equal to 1.4 Volts as stipulated in the floating charge while only a few cells still show the value of high battery charging rate of 1.5 Volt. In addition to the value of battery cell voltage, also obtained the results of calculation of efficiency through the data obtained. Efficiency of UPS (Uninterruptible Power Supply) at PT. Pupuk Sriwidjaja has a minimum efficiency of 76% obtained on January 7, 2019 while the maximum efficiency of 93% is obtained on January 14, 2019.
Item Type: | Thesis (Undergraduate) |
---|---|
Uncontrolled Keywords: | UPS, Battery, Charging, Efficiency |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering |
Divisions: | 03-Faculty of Engineering > 20201-Electrical Engineering (S1) |
Depositing User: | Users 1207 not found. |
Date Deposited: | 08 Aug 2019 05:12 |
Last Modified: | 08 Aug 2019 05:12 |
URI: | http://repository.unsri.ac.id/id/eprint/3028 |
Actions (login required)
View Item |